耐火試驗中電纜橋架的耐火時間是如何規(guī)定的?
根據(jù) GB 29415—2013《耐火電纜槽盒》,電纜橋架耐火時間分為 4 個等級:
According to GB 29415-2013 "Fire resistant Cable Tray Boxes", the fire resistance time of cable trays is divided into four levels:
F1:大于等于 90 分鐘。
F1: Greater than or equal to 90 minutes.
F2:大于等于 60 分鐘。
F2: Greater than or equal to 60 minutes.
F3:大于等于 45 分鐘。
F3: Greater than or equal to 45 minutes.

F4:大于等于 30 分鐘。
F4: Greater than or equal to 30 minutes.
另外,也有資料將電纜橋架的耐火等級分為 NI、NII、NIII 三個等級,其中 NI 等級耐火時間大于等于 60 分鐘,NII 等級大于等于 45 分鐘,NIII 等級大于等于 30 分鐘。
In addition, there are also materials that classify the fire resistance level of cable trays into three levels: NI, NII, and NIII. Among them, the fire resistance time of NI level is greater than or equal to 60 minutes, NII level is greater than or equal to 45 minutes, and NIII level is greater than or equal to 30 minutes.
不同使用環(huán)境對防火橋架的耐火時間要求有所不同,如地下車庫等對防火有特別要求的地段,防火橋架耐火時間要求大于 1 小時。在實際應(yīng)用中,應(yīng)根據(jù)具體的工程需求和相關(guān)規(guī)范來選擇合適耐火時間的電纜橋架。
The fire resistance time requirements for fire-resistant cable trays vary depending on the usage environment. For example, in underground garages and other areas with special fire protection requirements, the fire resistance time of fire-resistant cable trays should be greater than 1 hour. In practical applications, cable trays with appropriate fire resistance time should be selected based on specific engineering requirements and relevant specifications.
下一篇:耐火試驗后電纜橋架的性能和質(zhì)量如何評估?
相關(guān)文章 / Recommended news
- 山東省內(nèi)的家用電纜橋架使用壽命一般是多久?
- 怎么維護保養(yǎng)家用的濟南電纜橋架?
- 怎么檢測山東電纜橋架的承載能力?
- 怎么判斷濟南電纜橋架的耐火等級?
- 山東電纜橋架的材質(zhì)選擇需根據(jù)敷設(shè)環(huán)境的特點進行匹配
- 山東電纜橋架線槽什么情況下設(shè)置和不設(shè)置跨接線的要求
- 全長大于30米的電纜橋架,中間增加與保護導(dǎo)體的連接怎么做?
- 山東電纜橋架的安裝要求
- 濟南電纜橋架內(nèi)電纜的固定應(yīng)符合相關(guān)標(biāo)準(zhǔn)規(guī)范的規(guī)定
- 地下室山東橋架安裝檢查驗收標(biāo)準(zhǔn)、驗收節(jié)點
濟南電纜橋架到底需不需要跨接
安裝橋架
安裝橋架
安裝橋架
防火橋架